SikaHyflex®-105
SILICONE WEATHER-SEALANT FOR CURTAIN WALL, METAL CLADDING AND WINDOW INSTALLATION APPLICATIONS
SikaHyflex®-105 is a silicone based, 1-component, UV-stable, moisture-curing, elastic weather-sealant. Suitable for use in hot and tropical climatic conditions.
- Very good resistance to weathering
- Movement capability of ± 35 % (ASTM C 719)
- Easy to smooth and good workability
- Good adhesion to a wide range of substrates
Usage
SikaHyflex®-105 is designed for movement and connection joints in building envelopes such as curtain wall and metal cladding weather sealing applications.Advantages
- Very good resistance to weathering
- Movement capability of ± 35 % (ASTM C 719)
- Easy to smooth and good workability
- Good adhesion to a wide range of substrates
Packaging
600 mL foil pack, 20 foil packs per box
300 mL cartridges, 12 cartridges per box
Colour
Black, White, Middle Grey, Dark Grey, Beige and Brown
Product Details
SUSTAINABILITY
SikaHyflex®-105 conforms to LEED® EQc 4.1
- VOC content < 50 g/l (US EPA Method 24)
- SCAQMD, Rule 1168
- BAAQMD, Reg. 8, Rule 51
APPROVALS / CERTIFICATES
- ASTM C 920, class 35
- EN 15651-1 F EXT-INT CC 25 LM
- EN 15651-2 G CC 25 LM
- ISO 11600 F 25 LM & G 25 LM
Composition
Neutral cure silicone
Shelf life
SikaHyflex®-105 has a shelf life of 12 months from the date of production, if it is stored in undamaged, original, sealed packaging, and if the storage conditions are met.
Storage conditions
SikaHyflex®-105 shall be stored in dry conditions, where it is protected from direct sunlight and at temperatures between +5 °C and +25 °C.
Density
~1.35 kg/l | (ISO 1183-1) |
Compatibility
SikaHyflex®-105 is compatible with most SikaHyflex® and Sikasil® silicone weather sealants. All other sealants and adhesives have to be approved by Sika before using them in direct contact with SikaHyflex®-105.
Where two or more different reactive sealants and/or adhesives are used, allow the first one to cure completely before applying the next one. For specific information regarding compatibility contact our Technical Department.
Shore A Hardness
~26 (after 28 days) | (ISO 868) |
Secant Tensile Modulus
~0.30 N/mm2 at 100 % elongation (23 °C) | (ISO 8339) |
~0.40 N/mm2 at 100 % elongation (−20 °C) |
Elastic Recovery
~75 % | (ISO 7389) |
Tear Propagation Resistance
~3.5 N/mm | (ISO 34) |
Movement Capability
± 35 % | (ASTM C 719) |
Service Temperature
-40 °C min. / +150 °C max.
Joint Design
The joint width must be designed to suit the joint movement required and the movement capability of the sealant. The joint width shall be ≥ 6 mm and ≤ 45 mm. The joint depth shall be ≥ 6 mm and ≤ 15 mm. A width to depth ratio of 2:1 must be maintained (for exceptions, see table below).
Typical joint dimensions
Joint Width [mm] | Joint Depth [mm] |
6 | 6 |
10 | 6 |
15 | 8 |
20 | 10 |
30 | 15 |
45 | 15 |
All joints must be correctly designed and dimensioned in accordance with the relevant standards, before their construction. The basis for calculation of the necessary joint widths are the type of structure and its dimensions, the technical values of the adjacent building materials and the joint sealing material, as well as the specific exposure of the building and the joints.
For larger joints please contact our Technical Department.
Application
Backing Material
Use closed cell, polyethylene foam backing rods.
Sag Flow
~1 mm (20 mm profile at 50 °C) | (ISO 7390) |
Ambient Air Temperature
+5 °C min. / +40 °C max. (min. 3 °C above dew point temperature)
Substrate Temperature
+5 °C min. / +40 °C max.
Curing Rate
~3 mm/24 h (23 °C / 50 % r.h.) | (CQP 049-2) |
Skinning time
~40 min. (23 °C / 50% r.h.) | (CQP 019-1) |
Tack free time
~140 min. (23 °C / 50% r.h.) | (CQP 019-1) |
Consumption
Joint length [m] per 600 mL foil pack | Joint width [mm] | Joint depth [mm] |
16.7 | 6 | 6 |
10 | 10 | 6 |
5 | 15 | 8 |
3 | 20 | 10 |
2 | 25 | 12 |
1.3 | 30 | 15 |
1.1 | 35 | 15 |
1 | 40 | 15 |
0.9 | 45 | 15 |
SUBSTRATE PREPARATION
The substrate must be clean, dry, sound and homogeneous, free from oils, grease, dust and loose or friable particles. The following priming and/or pre-treatment procedures shall be followed:
Non-porous substrates
Float glass, coated glass, anodised aluminium and stainless steel have to be pre-treated using Sika® Aktivator-205, Sika® Aktivator-100 or Sika® Cleaner P. Powder coated and PVDF coated metals have to be pre-treated using Sika® Aktivator-205. For details like application and flash-off times refer to the most recent Product Data Sheet of the respective pre-treatment product.
Porous substrates
Concrete, aerated concrete and cement based renders, mortars and bricks shall be primed using Sika® Primer-3 N or Sika® Primer-210. For details like application and flash-off times refer to the most recent Product Data Sheet of the respective pre-treatment product.
Adhesion tests on project specific substrates must be performed prior to application. For more detailed advice and instructions please contact our Technical Department.
Note: Primers are adhesion promoters. They are neither a substitute for the correct cleaning of a surface, nor do they improve the strength of the surface significantly.
CLEANING OF EQUIPMENT
Clean all tools and application equipment immediately after use with Sika® Remover-208 and/or Sika® TopClean T. Once cured, residual material can only be removed mechanically.